SPECIFICATION
Emergency lighting shall be provided by using a quad or triple twin-tube compact fluorescent fixture equipped with a BAL650C-2
emergency ballast. This emergency ballast shall consist of a high-temperature, maintenance-free nickel cadmium battery, charger
and electronic circuitry contained in one 9 3/8" x 2 3/8" x 1 1/2" white metal case with two feet of flexible conduit at each end of the
ballast. A test switch/monitor plate with test switch and charging indicator light shall be provided to monitor the charger and battery.
The emergency ballast shall be capable of operating one 10W – 26W Quad or Triple tube 2-pin compact fluorescent lamp (with no
Integral starter) in the emergency mode for a minimum of 90 minutes. The BAL650C-2 shall have 3.5 Watts of input power, a 14.4
Watt-hour battery capacity, and comply with emergency standards set forth by the current NEC. The emergency ballast shall be UL
Listed for installation inside, on top of, or remote from the fixture, warranted for a full five years from date of purchase.